Emerson R48-2000e3 Rectifier Module
Emerson Rectifier Module R48-2000e3 Supply
R48-2000E3
AC InputVoltage :85 VAC to 300 VAC (see figure 1),
187 VAC to 264 VAC (nominal)
Frequency 45 Hz to 65 Hz
Maximum Current 12 A
Power Factor >0.99 from 50 to 100% load
Protection
High and low voltage protection, surge and lightning protection
Adapts to poor quality grid (voltage dip, weak mains)
Disconnection at 415 VAC
Mains fuses in both lines
DC Output Voltage -42 VDC to -58 VDC
Maximum Power 2000 W
Maximum Current 42 A @ -48 VDC, limit set point 0 to 42 A (see figure 2)Peak Efficiency 96.2%
Protection
Fuse for reverse connection and back feeding protection
High voltage shutdown
High temperature protection
Control and Monitoring
Converter Alarm and Signaling Alarm and status reported via CAN bus to system controller
Visual Indications
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Environmental
Operating -40°C to 80°C / -40°F to +176°F (see figure 3 for derating)
Temperature Derating
Full output power up to +65°C at input voltage range 200 to 250 VAC
(see figure 3)
Storage -40°C to +70°C / -40°F to +158°F
Relative Humidity 0 to 95%
Altitude Full output power up to +65°C at input voltage range @200~ 250 VAC
Standards Compliance
Safety 60950-1 (EN, IEC and UL)
EMC
EN55022, CISPR22, ETSI EN300 286: 2005, FCC CFR 47 Part 15,
Telcordia GR-1089-CORE issue 6 (Class B conducted and radiated)
Environment REACH, RoHS, WEEE
Mechanics
Dimensions: (H x W x D) 41 x 84.5 x 252.5 (mm) / 1.61 x 3.33 x 9.94 (inches)
Weight :1.13 kg / 2.49 lbs
Contact: Sam Chan
Phone: +86-130 5858 3139
E-mail: power@48vrectifier.com
Whatsapp:0086-13058583139
Add: Dongcheng Middle Road, Guancheng District, Dongguan City, Guangdong, 523000, China
We chat